Navigation:  HVAC Terminal Control >

Programmable Thermostats on Furnaces

Previous page Next page
  rev. 2008-12-07        

Existing Conditions

There are several natural gas fired furnaces located throughout the xxx building.  These furnaces are controlled by simple wall mounted thermostats, which control to a single setpoint all the times.

Retrofit Conditions

It is recommended that electronic setback thermostats be installed, to reset the space temperature of the shop areas to 15°C during unoccupied times.  Typically, space temperature during occupied periods would be set at 21°F for heating and 24°F for cooling.  During unoccupied periods temperature would be allowed to drift within a wider range (e.g. 18°C to 27°C).

<The supply fan would operate continuously during occupied periods.  It would cycle off in the unoccupied mode, only coming on when either heating or cooling were needed.>

<Because this unit has economizer damper control, we recommend using a thermostat that has 'damper override' capability.  This feature disables economizer damper operation during unoccupied mode, so that the dampers remain fully shut and the air handler does not bring in ventilation air.>

We recommend using a commercial grade "heating only" setback thermostat that takes power from a low-voltage control transformer.  Residential grade thermostats are typically less expensive, but they are less rugged, require battery replacement and are prone to corrosion of the battery contacts.

In most cases we would recommend allowing occupant access for fine-tuning of the setback schedule.  However, if occupant adjustment is not desirable, consider a thermostat with a password lockout to prevent undesired access.

Further Benefits

 

 

Application Details

If conditioning cannot be turned off during unoccupied hours, install temperature setback.

A basic energy conservation measure that saves energy during unoccupied periods.  A standard feature in most electronic control systems.  With other types of controls, it requires special thermostats.

Issues and Concerns

 

References

This recommendation is in accordance with Measure HV10 of the CMHC manual on Energy and Water Efficiency in Multi-Unit Residential Buildings  and with Section 6.3 Heating Ventilating and Air Conditioning Systems of the ASHRAE Standard on Energy Conservation in Existing Buildings.

 

Analysis

Sample bin analysis

 

 

 

 

 

Natural Gas Consumption

 

LOADS

Setback Bin Hours

Existing GJ Gas Consumption

Retrofit Consumption

Savings

Average F

Average C

DeltaT

Setback DeltaT

Total Bin Hours

Base

Winter

Total

Ngas Heating Load -  GJ/h

Setback Heating Load - GJ/h

7a-8p

8p-7a

7a-8p

8p-7a

Heating 8p-7a - GJ Gas

Heating GJ Gas Saved

23

-5

22

20

3

1

1

2

0.27

0.25

1.2

1.6

0

0

0

0

28

-3

20

18

97

18

23

52

0.24

0.22

21.3

75.6

5

18

16

2

33

0

17

15

551

101

118

266

0.21

0.19

167.9

383.4

36

82

72

10

38

3

14

12

1,034

189

191

447

0.19

0.16

435.6

597.9

81

111

95

16

43

6

11

9

1,503

275

235

575

0.16

0.13

744.7

758.4

117

119

98

21

48

9

8

6

1,539

282

197

513

0.13

0.10

751.8

787.3

96

101

77

24

53

11

6

4

1,503

275

150

426

0.10

0.06

707.6

795.3

71

79

51

28

58

14

3

1

1,202

220

86

281

0.07

0.02

713.8

488.6

51

35

10

25

63

17

0

-2

752

138

32

138

0.04

0.00

640.1

112.0

27

5

0

5

68

20

-3

-5

381

70

5

70

0.01

0.00

367.0

13.5

5

0

0

0

73

23

-6

-8

148

27

0

27

0.00

0.00

146.4

1.3

0

0

0

0

78

25

-8

-10

32

6

0

6

0.00

0.00

31.7

0.0

0

0

0

0

83

28

-11

-13

15

3

0

3

0.00

0.00

15.0

0.0

0

0

0

0

88

31

-14

-16

1

0

0

0

0.00

0.00

1.0

0.0

0

0

0

0

93

34

-17

-19

0

0

0

0

0.00

0.00

0.0

0.0

0

0

0

0

98

36

-19

-21

0

0

0

0

0.00

0.00

0.0

0.0

0

0

0

0

0

0

 

 

8,760

1,604

1,039

2,806

 

 

4,745

4,015

489

550

419

131

 

 



opp_ProgrammableThermostatsonFurnaces         ©2017 Managing Energy Inc.